Specification \ Model
|
Air-to-Water Heat Pump
|
Water-to-Water Heat Pump
|
FCP-30A
|
FCP-75A
|
FCP-30W
|
FCP-75W
|
Power
|
V
|
3φ 220V/380V 50/60Hz
|
Outlet temperature
|
℃
|
90
|
65
|
90
|
65
|
90
|
65
|
90
|
65
|
Heating capacity
|
kw
|
23/27.2
|
27/31
|
60/69
|
68/79
|
23/27
|
27/31.5
|
60.2/69.6
|
67/78
|
Hot water outflow
|
L/min
|
3.8/4.2
|
7.7/9.0
|
10/13.2
|
22/26
|
3.8/4.2
|
7.5/8.8
|
10/13.2
|
21/24
|
Cooling capacity
|
kw
|
|
|
|
|
18.2
|
20.6
|
47
|
54
|
Cold water outflow
|
L/min
|
|
|
|
|
44
|
47
|
132
|
140
|
Power consume
|
kw
|
6.7/8.7
|
6.3/7.4
|
19.5/24
|
17/21
|
6.7/8.7
|
6.2/7.1
|
19.5/24.8
|
15.4/19.8
|
220V Running current
|
A
|
24.3/26.8
|
23/25
|
68/79
|
67/75
|
23/26
|
22/24
|
68/79
|
67/75
|
380V Running current
|
A
|
13/15.8
|
12.6/15
|
33.5/39
|
31.4/37
|
13/15
|
12/14.5
|
33.5/39
|
31.4/37
|
220V Running current
|
A
|
190/189
|
351/447
|
190/189
|
351/447
|
380V Running current
|
A
|
83/173
|
215/255
|
83/173
|
215/255
|
Temperature range
|
℃
|
55~90℃
|
Compressor
|
Type
|
|
Reciprocating half closed
|
Output
|
kw
|
6.0/7.2
|
15/18
|
6.0/7.2
|
15/18
|
Oil heater
|
W
|
100
|
140
|
100
|
140
|
Blower
|
W
|
DC310V90 WX2
|
450X2
|
|
Hot water pump
|
W
|
DC310V 72W
|
1580
|
BLDC motor DC310V-72(30A) / C1580(75A)
|
Cold water pump
|
W
|
|
450/560
|
850/1270
|
Heat exchanger
|
|
Propeller dual pipe/stainless steel plate
|
Evaporator
|
|
Enforce air heat exchange
|
Stainless steel plate
|
Refrigerant pressure
|
|
High pressure side15MPa/ low pressure side 8MPa
|
High pressure side 14.5MPa/ Low pressure side7.5MPa
|
Refrigerant / fill
|
kg
|
CO2(R744)/7.2kg
|
CO2(R744)/13.6kg
|
CO2(R744)/7.5kg
|
CO2(R744)/14.2kg
|
Coefficient of performance
|
COP
|
3.4/3.1
|
4.1/4.1
|
3.0/2.87
|
4/3.8
|
7.9/7.8
|
8.2/8.3
|
7.6/7.8
|
8.2/8.2
|
Device Protection
|
|
High & low pressure switch/sensor 、compressor safety valve、over current relay、motor over heat protection、 over heat detection、Inverted/open phase prevention
|
Running noise
|
dB
|
54
|
62
|
52
|
62
|
Hot water pipe diameter
|
|
PT1"(25A)
|
PT1 ¼"(35A)
|
PT1"(25A)
|
PT1 ¼"(35A)
|
Cold water pipe diameter
|
|
|
|
PT1 ¼"(35A)
|
PT1 ½"(40A)
|
Size
|
mm
|
W1465xD950xH1870
|
W2005xD1050xH2040
|
W1465xD947xH1400
|
W1465xD947xH1400
|
Weight
|
kg
|
630
|
1130
|
475
|
820
|
Coating Color
|
|
White and Red
|
Note: Above information in laboratory testing conditions as following:
1. Heating capacity condition A: Outside temperature DB=7℃, WB=6℃, inlet water=9℃, outlet water=90℃.
Heating capacity condition B: Outside temperature DB=16℃, WB=12℃, inlet water=17℃, outlet water=65℃.
2.Water cooling condition: inlet water=12℃, outlet water=7℃
3.Running noise is tested 1M in front of machine and 1.5M from ground.
4.The specification may be changed according market requirement.
5.Any special request shall be informed before the order is confirmed.
6.Inlet water pressure shall be in the rage of 0.005 to 0.4Mpa. Release valve shall be installed if the pressure is high.
|