R410a Series Heat Pump-Table2 ✖Close Window

R410a Series (Air-to-Water) Heat Pump

 

Specification \ Model

FHP-5A4A

FHP-8A4A

FHP-10A4A

FHP-12A4A

FHP-15A4A

FHP-15A4B

FHP-20A4B

FHP-25A4B

FHP-30A4B

FHP-35A4D

FHP-40A4B

FHP-50A4B

FHP-60A4B

Power

3φ220/380/440V 60 Hz

Heating capacity

KW

17.5

27

36

43

52

54

72

85

104

124

144

171

209

Size

H

mm

1390

1790

1870

1870

2040

2040

2040

2040

2040

2140

2140

2250

2250

W

mm

1020

1465

1465

1465

2005

2005

2005

2005

2005

2928

2928

2100

2100

D

mm

370

947

950

950

1050

1050

1050

1050

1050

1050

1050

2000

2000

Running current

A

20.3/11.8/10.2

29.7/82.9/71.6

36.6/21.2/18.3

41.9/24.3/21.0

54.5/31.6/27.3

55.5/32.1/27.8

71.6/41.5/35.8

88.9/51.5/44.5

113.0/65.4/56.5

137.2/79.4/68.6

143.7/83.2/71.9

152/88/76

200/115.8/100

Power consume

KW

5.46

8.28

10.73

12.83

16.86

16.58

21.46

25.66

33.72

38.82

42.92

51.32

67.44

COP

W/W

3.19

3.26

3.37

3.33

3.10

3.26

3.37

3.33

3.10

3.20

3.37

3.33

3.10

Compressor

Type

Hermetic-scroll

Quantity

1

1

1

1

1

2

2

2

2

2

4

4

4

Capacity adjustment(%)

100,0%

100,50,0%

Start-up

Sequential

Sequential

Evaporator

Type

Fin and Tube type

Type of Fan

Propeller type

Motor power W

104X2

390

243

243

390

390

390

450

770

770

380

450

770

Number of fan and motor

2

1

2

2

2

2

2

2

2

2

4

4

4

Wind direction

Front-Side

Top-Side

Heater

Type

Flat/ shell tube exchanger

Water Flow L/min

48

78

102

122

150

150

207

245

298

355

413

490

599

Pipe diameter

PT 1 B

PT 1 ½ B

PT 1 ½ B

PT 2 B

PT 2 B

PT 2 B

PT 2 B

PT 2 ½ B

PT 2 ½ B

PT 2 ½ B

PT 2 ½ B

PT 3 B

PT 3 B

Internal water pump head (M)

24

23

22

20

18

18

22

19

22

21

20

19

21

Device Protection

High & low pressure switch、defrost protection、fan motor over heat protection 、phase reverse relay、 compressor over load protection、safety valve、pump over load protection

Refrigerant

R140a

Weight

kg

145

320

340

385

460

495

510

600

685

890

1250

1320

1470


Note: 1. Heat generation testing standard: heat water from 45 to 50. The environment is 20 DB, 15 WB.

2. Suggest the hot water outlet under 57.

3. Water pump is excluded in Power consumption and COP calculation. Please contact with the business division for any special manufacture requirement

4. Efficiency unit is 1KW = 860 Kcal/hr