R410a Series Heat Pump-Table1 ✖Close Window

R410a Series (Water-to-Water) Heat Pump


Specification\Model

FHP-8W4A

FHP-10W4A

FHP-12W4A

FHP-15W4A

FHP-20W4B

FHP-25W4B

FHP-30W4B

FHP-35W4B

FHP-45W4D

FHP-55W4D

Power

3φ220/380/440V 60 Hz

Heating capacity

KW

26

35

42

50

69

83

100

118

162

197

Cooling capacity

KW

18

24

28

34

48

57

67

81

114

134

Running current

A

24/14/12

31/18/16

36/21/18

46/27/231

61/35/31

71/41/36

92/53/46

114/66/57

142/82/71

185/107/93

Power consume

KW

7.5

10.0

12.0

15.5

20.5

24.0

31.5

36.5

48.5

63.0

 

COP

KW/KW

5.73

5.80

5.75

5.35

5.70

5.75

5.27

5.45

5.69

5.25

Size

H

mm

1400

1400

1400

1400

1400

1500

1500

1750

1750

1750

W

mm

1465

1465

1465

1465

1465

1850

1850

2500

2500

2500

D

mm

947

947

947

947

947

947

947

947

1500

1500

Hot water outflow

LPM

70

100

120

140

200

235

285

340

465

565

Cold water outflow

LPM

50

70

80

100

140

165

195

230

325

385

Compressor

Type

Hermetic-scroll

Quantity

1

1

1

1

2

2

2

2

4

4

Capacity adjustment(%)

100,0%

100,0%

100,0%

100%

100,50,0%

100,50,0%

100,50,0%

100,50,0%

100,75,50,25,0%

100,75,50,25,0%

Start-up

Direct

Sequential

Type of heater

Flat/ shell tube exchanger

Type of evaporator

Flat/ shell tube exchanger

Device Protection

High & low pressure switchfreeze up protection over current relay phase reverse relaycompressor over load protection

Pipe diameter

Hot water in/outlet

FPT

1-½"

1-½"

1-½"

1-½"

2"

2"

2"

2"

3"

3"

Cold water in/outlet

FPT

1-½"

1-½"

1-½"

1-½"

2"

2"

2"

2"

3"

3"

Sluice pipe

FPT

3/4"

Refrigerant

R410a

Refrigerant Control

Electric expansion valve /Outer thermostatic expansion valve

Weight

kg

330

380

445

480

600

650

680

740

1480

1620



Note: 1. Efficiency means how much degree the system can raise for heating function to heat water from 45℃ to 50℃ or it can lower for cooling function to cool water from 12℃ to 7℃.

2. Control mode: it will stop the compressor when the temperature reach the configured degree.

3. Suggest to set the outlet water degree under 57

4. Water pump is not included in standard system

5. Efficiency unit is 1KW = 860 Kcal/hr