R134a Series Heat Pump-Table2 ✖Close Window

Specification\Model

FHP-5A1A

FHP-6A1A

FHP-8A1A

FHP-10A1A

FHP-12A1A

FHP-12A1B

FHP-15A1B

FHP-20A1B

FHP-25A1B

FHP-30A1C

FHP-40A1D

FHP-50A1D

Power

3φ220/380/440V 60 Hz

Heating capacity

KW

18.2

23.4

27.5

34

41.2

47.0

54.5

68.8

82.3

103.2

137.6

164.7

Size

H

mm

1790

1790

1870

1870

1870

2040

2040

2040

2040

2140

2140

2250

W

mm

1465

1465

1465

1465

1465

2005

2005

2005

2005

2928

2928

2100

D

mm

947

947

950

950

950

950

1050

1050

1050

1050

1050

2000

Running current

A

23.4/13.5/11.7

28.0/16.2/14.0

32.8/19.0/16.4

41.8/24.4/20.9

50.4/30.3/26.2

54.8/31.7/27.4

63.7/36.9/31.9

89.4/51.8/44.7

110/63.7/55

114.7/66.4/57.4

153/88.6/76.5

194.2/112.4/97.1

Power consume

KW

6.03

7.68

9.03

11.2

13.86

15.36

18.06

23.72

27.7

34.3

47.4

55.44

COP

W/W

3.02

3.05

3.01

3.04

2.97

3.05

3.02

2.90

2.97

3.01

2.95

2.97

Compressor

Type

Hermetic-scroll

Quantity

1

1

1

1

1

2

2

2

2

3

4

4

Capacity adjustment(%)

100,0%

100,0%

100,0%

100,0%

100,0%

100,50,0%

100,50,0%

100,50,0%

100,50,0%

100,67.33,0%

100,75,50,25,0%

100,75,50,25,0%

Start-up

direct

Sequential

Evaporator

Type

Hermetic-scroll

Type of Fan

Propeller type

Motor power

355

355

450

243

243

390

450

450

770

770

460

770

Number of fan and motor

1

1

1

2

2

2

2

2

2

3

4

4

Wind direction

Front side

Top side

Heater

Type

Flat/ shell tube exchanger

Water Flow L/min

52

67

78

99

118

134

156

197

236

312

395

472

Pipe diameter

PT 1

PT 1 ¼

PT 1 ½

PT 1 ½

PT 1 ½ B

PT 1 ½ B

PT 2 B

PT 2 B

PT 2 ½

PT 2 ½ B

PT 2 ½

PT 3

MInternal water pump head (M)

24

18

24

22

21

20

23

22

22

20

18

17

Device Protection

High & low pressure switch、defrost protection、fan motor over heat protection 、phase reverse relay、 compressor over load protection、safety valve、pump over load protection

Refrigerant

R-134a

Weight

kg

315

330

360

400

410

520

570

640

800

980

1350

1510


 

 

Note: 1. Heat generation testing standard: heat water from 50 to 55. The environment is 20 DB, 15 WB.

2. Suggest the hot water outlet under 57.

3. Water pump is excluded in Power consumption and COP calculation. Please contact with the business division for any special manufacture requirement

4. Efficiency unit is 1KW = 860 Kcal/hr