Specification\Model
|
FHP-5A1A
|
FHP-6A1A
|
FHP-8A1A
|
FHP-10A1A
|
FHP-12A1A
|
FHP-12A1B
|
FHP-15A1B
|
FHP-20A1B
|
FHP-25A1B
|
FHP-30A1C
|
FHP-40A1D
|
FHP-50A1D
|
Power
|
3φ220/380/440V 60 Hz
|
Heating capacity
|
KW
|
18.2
|
23.4
|
27.5
|
34
|
41.2
|
47.0
|
54.5
|
68.8
|
82.3
|
103.2
|
137.6
|
164.7
|
Size
|
H
|
mm
|
1790
|
1790
|
1870
|
1870
|
1870
|
2040
|
2040
|
2040
|
2040
|
2140
|
2140
|
2250
|
W
|
mm
|
1465
|
1465
|
1465
|
1465
|
1465
|
2005
|
2005
|
2005
|
2005
|
2928
|
2928
|
2100
|
D
|
mm
|
947
|
947
|
950
|
950
|
950
|
950
|
1050
|
1050
|
1050
|
1050
|
1050
|
2000
|
Running current
|
A
|
23.4/13.5/11.7
|
28.0/16.2/14.0
|
32.8/19.0/16.4
|
41.8/24.4/20.9
|
50.4/30.3/26.2
|
54.8/31.7/27.4
|
63.7/36.9/31.9
|
89.4/51.8/44.7
|
110/63.7/55
|
114.7/66.4/57.4
|
153/88.6/76.5
|
194.2/112.4/97.1
|
Power consume
|
KW
|
6.03
|
7.68
|
9.03
|
11.2
|
13.86
|
15.36
|
18.06
|
23.72
|
27.7
|
34.3
|
47.4
|
55.44
|
COP
|
W/W
|
3.02
|
3.05
|
3.01
|
3.04
|
2.97
|
3.05
|
3.02
|
2.90
|
2.97
|
3.01
|
2.95
|
2.97
|
Compressor
|
Type
|
Hermetic-scroll
|
Quantity
|
1
|
1
|
1
|
1
|
1
|
2
|
2
|
2
|
2
|
3
|
4
|
4
|
Capacity adjustment(%)
|
100,0%
|
100,0%
|
100,0%
|
100,0%
|
100,0%
|
100,50,0%
|
100,50,0%
|
100,50,0%
|
100,50,0%
|
100,67.33,0%
|
100,75,50,25,0%
|
100,75,50,25,0%
|
Start-up
|
direct
|
Sequential
|
Evaporator
|
Type
|
Hermetic-scroll
|
Type of Fan
|
Propeller type
|
Motor power
|
355
|
355
|
450
|
243
|
243
|
390
|
450
|
450
|
770
|
770
|
460
|
770
|
Number of fan and motor
|
1
|
1
|
1
|
2
|
2
|
2
|
2
|
2
|
2
|
3
|
4
|
4
|
Wind direction
|
Front side
|
Top side
|
Heater
|
Type
|
Flat/ shell tube exchanger
|
Water Flow L/min
|
52
|
67
|
78
|
99
|
118
|
134
|
156
|
197
|
236
|
312
|
395
|
472
|
Pipe diameter
|
PT 1
|
PT 1 ¼
|
PT 1 ½
|
PT 1 ½
|
PT 1 ½ B
|
PT 1 ½ B
|
PT 2 B
|
PT 2 B
|
PT 2 ½
|
PT 2 ½ B
|
PT 2 ½
|
PT 3
|
MInternal water pump head (M)
|
24
|
18
|
24
|
22
|
21
|
20
|
23
|
22
|
22
|
20
|
18
|
17
|
Device Protection
|
High & low pressure switch、defrost protection、fan motor over heat protection 、phase reverse relay、 compressor over load protection、safety valve、pump over load protection
|
Refrigerant
|
R-134a
|
Weight
|
kg
|
315
|
330
|
360
|
400
|
410
|
520
|
570
|
640
|
800
|
980
|
1350
|
1510
|
Note: 1. Heat generation testing standard: heat water from 50℃ to 55℃. The environment is 20℃ DB, 15℃ WB.
2. Suggest the hot water outlet under 57℃.
3. Water pump is excluded in Power consumption and COP calculation. Please contact with the business division for any special manufacture requirement
4. Efficiency unit is 1KW = 860 Kcal/hr
|
|
|