R134a Series Heat Pump-Table1 ✖Close Window

R134a(Water-to-Water) Heat Pump

High water temerature for hot environment

 Cycling heat pump can heat the water to 70℃, the differential of inlet and outlet water is 5 to 10℃

Direct heat pump can heat the water to 85℃, the differential of inlet and outlet water is 5 to 70℃


Specification\Model

FHP-8W1A

FHP-10W1A

FHP-12W1A

FHP-15W1B

FHP-20W1B

FHP-25W1B

FHP-30W1D

FHP-40W1D

Power

3φ220/380/440V 60 Hz

Heating capacity

KW

26

32

39

51

65

78

103

130

Cooling capacity

KW

17

22

26

35

43

52

69

87

Running current

A

26/15/13

44/25/22

45/26/23

53/31/27

87/50/44

90/52/45

106/61/53

174/100/87

Power consume

KW

8.5

10.5

12.5

16.5

21.5

25.5

33.5

43.0

COP

KW/KW

5.06

5.14

5.20

5.21

5.02

5.10

5.13

5.05

Size

H

mm

1400

1400

1400

1400

1400

1400

1750

1750

W

mm

1465

1465

1465

1465

1465

1465

2530

2530

D

mm

947

947

947

947

947

947

1500

1500

Hot water outflow

LPM

75

90

110

145

185

225

300

370

Cold water outflow

LPM

50

65

75

100

125

150

220

250

Compressor

Type

Hermetic-scroll

Quantity

1

1

1

2

2

2

4

4

Capacity adjustment(%)

100,0%

100,0%

100,0%

100,50,0%

100,50,0%

100,50,0%

100,75,50,25,0%

100,75,50,25,0%

Start-up

direct

Type of heater

flat/ shell tube exchanger

Type of evaporator

flat/ shell tube exchanger

Device Protection

High & low pressure switch、freeze up protection 、 over current relay 、phase reverse relay、 compressor over load protection

Pipe diameter

Hot water in/outlet

FPT

1-1/2"

1-1/2"

1-1/2"

2"

2"

2"

2-1/2"

3B

Cold water in/outlet

FPT

1-1/2"

1-1/2"

1-1/2"

2"

2"

2"

2-1/2"

3B

Sluice pipe

FPT

3/4"

Refrigerant

R-134a

Refrigerant Control

Electric expansion valve /Outer thermostatic expansion valve

Weight

kg

410

445

480

550

580

620

1240

1360



Note:  1. Efficiency means how much degree the system can raise for heating function to heat water from 50℃ to 50℃ or it can lower for cooling  function to cool water from 12℃ to 7℃.
   2. Control mode: it will stop the compressor when the temperature reach the configured degree.
   3. Suggest to set the outlet water degree under 57℃.
     4. Water pump is not included in standard system.
     5. Efficiency unit is 1KW = 860 Kcal/hr.