項目 \ 機種
|
FHP-5A4A
|
FHP-8A4A
|
FHP-10A4A
|
FHP-12A4A
|
FHP-15A4A
|
FHP-15A4B
|
FHP-20A4B
|
FHP-25A4B
|
FHP-30A4B
|
FHP-35A4D
|
FHP-40A4B
|
FHP-50A4B
|
FHP-60A4B
|
電 源
|
3φ220/380/440V 60 Hz
|
製熱能力
|
KW
|
17.5
|
27
|
36
|
43
|
52
|
54
|
72
|
85
|
104
|
124
|
144
|
171
|
209
|
尺
寸
|
H
|
mm
|
1390
|
1790
|
1870
|
1870
|
2040
|
2040
|
2040
|
2040
|
2040
|
2140
|
2140
|
2250
|
2250
|
W
|
mm
|
1020
|
1465
|
1465
|
1465
|
2005
|
2005
|
2005
|
2005
|
2005
|
2928
|
2928
|
2100
|
2100
|
D
|
mm
|
370
|
947
|
950
|
950
|
1050
|
1050
|
1050
|
1050
|
1050
|
1050
|
1050
|
2000
|
2000
|
運轉電流
|
A
|
20.3/11.8/10.2
|
29.7/82.9/71.6
|
36.6/21.2/18.3
|
41.9/24.3/21.0
|
54.5/31.6/27.3
|
55.5/32.1/27.8
|
71.6/41.5/35.8
|
88.9/51.5/44.5
|
113.0/65.4/56.5
|
137.2/79.4/68.6
|
143.7/83.2/71.9
|
152/88/76
|
200/115.8/100
|
消耗電力
|
KW
|
5.46
|
8.28
|
10.73
|
12.83
|
16.86
|
16.58
|
21.46
|
25.66
|
33.72
|
38.82
|
42.92
|
51.32
|
67.44
|
COP
|
W/W
|
3.19
|
3.26
|
3.37
|
3.33
|
3.10
|
3.26
|
3.37
|
3.33
|
3.10
|
3.20
|
3.37
|
3.33
|
3.10
|
壓
縮
機
|
型式
|
渦卷式
|
數量
|
1
|
1
|
1
|
1
|
1
|
2
|
2
|
2
|
2
|
2
|
4
|
4
|
4
|
能力調整(%)
|
100,0%
|
100,50,0%
|
啟動方式
|
直接順序啟動
|
直接順序啟動
|
蒸
發
徑
|
型式
|
鰭片盤管式
|
風扇型式
|
螺旋式
|
馬達出力W
|
104X2
|
390
|
243
|
243
|
390
|
390
|
390
|
450
|
770
|
770
|
380
|
450
|
770
|
風扇及馬達數量
|
2
|
1
|
2
|
2
|
2
|
2
|
2
|
2
|
2
|
2
|
4
|
4
|
4
|
吹出風向
|
前側方吹出
|
上方吹出
|
熱
水
器
|
型式
|
板式/殼管式
|
水量 L/min
|
48
|
78
|
102
|
122
|
150
|
150
|
207
|
245
|
298
|
355
|
413
|
490
|
599
|
配管口徑
|
PT 1 B
|
PT 1 ½ B
|
PT 1 ½ B
|
PT 2 B
|
PT 2 B
|
PT 2 B
|
PT 2 B
|
PT 2 ½ B
|
PT 2 ½ B
|
PT 2 ½ B
|
PT 2 ½ B
|
PT 3 B
|
PT 3 B
|
內置水泵提程M
|
24
|
23
|
22
|
20
|
18
|
18
|
22
|
19
|
22
|
21
|
20
|
19
|
21
|
保護裝置
|
高壓開關、低壓開關、除霜保護、壓縮機內置過熱保護、風扇馬達過熱保護、防止逆轉繼電器、安全閥、水泵過載保護
|
冷媒
|
R140a
|
重 量
|
kg
|
145
|
320
|
340
|
385
|
460
|
495
|
510
|
600
|
685
|
890
|
1250
|
1320
|
1470
|
註:1.能力係指熱入水溫50℃,出水溫55℃,冰水入水溫12℃,出水溫7℃之能力。
2.控制模式:熱水溫到達,壓縮機皆停止運轉。
3.建議熱水出溫度低於57℃。
4.標準機組未含水泵,若需水泵請另行通知,並機組外型依水泵有所變更。
5.能力單位1KW=860 Kcal / hr。
|
|
|